Abstract

This study aims to find out about the procedure for measuring the isolation resistance of the main equipment of the 150 kV conventional substation (AIS) as many as 5 bays at the Panakkukang Substation through the measurement of the insulation resistance value in accordance with the predetermined standards. The method used in this study is quantitative descriptive. The subject of the study to be studied is a comparison of isolation resistance values in pre- and post-treatment. This was done to find out if there was a change in the insulation resistance value of the main equipment of the Substation. The main equipment studied is LA, PMT, CT, VT, and Transformer. Measurements were taken with a Megger measuring instrument, with a voltage injection of 5kV. For 5kV voltage injection, the maximum value of the test device is >1000 GΩ. The standard used is IEEE 43-2000, which is > 1 MΩ / 1 kV. Based on the results of research that has been carried out on each main equipment of the substation at GI Panakkukang. It can be concluded that the isolation resistance value in each main equipment of the substation at GI Panakkukang is above the minimum value (> MΩ/1 KV) in accordance with the IEEE Std 62: 1995 standard, VDE Catalogue 228/4, and the standard used by PLN in the "Power System Maintenance Guidebook" in 2014 the isolation resistance value at each main substation at GI Panakkukang has increased after being maintained. Maintenance can be carried out by cleaning the equipment body and foreign materials, and measuring the insulation resistance periodically.

References

Ababil, K. (2023). Analisa perbandingan kelayakan tahanan isolasi transformator daya menggunakan pengujian indeks polaritas, tangen delta, BDV (breakdown voltage), dan rasio tegangan di gardu induk 150 kV Ulee Kareng. 20–30.

Amalia, S. (2017). Analisis pemeliharaan lightning arrester pada gardu induk GIS Simpang Haru Padang.

Ananto, R. A., Arifin, K. S., Hermawan, A., & Efendrik, P. (2023). Kajian teknis pemeliharaan transformator arus pada gardu induk PLTU Tanjung Awar-Awar Babat. Jurnal Sistem Kelistrikan, 2–5.

Ardianto, Firdaus, & Noveri, L. M. (2024). Analisis kinerja sistem proteksi berdasarkan frekuensi gangguan di gardu induk 150 kV Garuda Sakti.

Azis, A., & Febrianti, I. K. (2019). Analisis sistem proteksi arus lebih pada penyulang Cendana gardu induk Bungaran Palembang. Jurnal Ampere.

Efryansah, R. A. (2023). Analisis kualitas tahanan isolasi pada transformator dengan preventive maintenance gardu induk Garuda Sakti.

Fadillah, F. C. (2019). Analisis hasil pengujian tahanan isolasi transformator daya berdasarkan hasil uji indeks polarisasi dan tangen delta.

Firdaus, Mappeasse, M. Y., Mangesa, R. T., Yantahin, M., & Miru, A. S. (2023). Analisis hasil pengukuran tahanan isolasi pada pemutus tenaga (PMT) kubikel 20 kV di gardu induk Jeneponto. Jurnal Media Elektrik, 1–5.

Ganta, W. (2021). Sistem proteksi gardu induk.

Mulyanto, B., Situmeang, U., & Halilintar, M. P. (2022). Analisis kondisi tahanan isolasi transformator daya 125 MVA menggunakan indeks polarisasi tangen delta dan breakdown voltage di PLTU Tenayan Raya 2 x 110 MW.

Nugroho, W. (2019). Pengujian tahanan isolasi pada pemeliharaan pemutus tenaga gas SF6 bay Purworejo gardu induk 150 kV Bantul.

Saputra, A. D., & Rahmadewi, R. (2022). Pengujian tahanan isolasi capacitive voltage transformer (CVT) 500 kV bay GT 2 dalam upaya meningkatkan peralatan proteksi di GITET Muara Tawar.

Siregar, S. B., & Rahmadewi, R. (2021). Pengujian tahanan isolasi trafo tegangan di gardu induk Telukjambe Karawang. 25–35.

Tambingon, J. J., Mangindaan, G., & Patras, L. (2022). Analysis of lightning arrester equipment in 150 kV GIS Teling.

Tapparan, A. G. (2020). Analisa tahanan isolasi transformator arus (CT) bay trafo 1 gardu induk 150 kV Pati. 2–10.

Wijayanti, A. N. (2019). Analisis tahanan isolasi pada transformator di gardu induk 150 kV Jekulo, Surakarta.

Published

2024-08-09

How to Cite

Fandi Rahman, Muh. Fitrah, Suryani Suryani, & Hafsah Nirwana. (2024). Analisis Tahanan Isolasi Peralatan Utama Gardu Induk Panakkukang. Globe: Publikasi Ilmu Teknik, Teknologi Kebumian, Ilmu Perkapalan, 2(3), 237–249. https://doi.org/10.61132/globe.v2i3.507

Similar Articles

<< < 1 2 3 > >> 

You may also start an advanced similarity search for this article.